380 Class Explosive Atmosphere Flourescent Fixture

380 Class Explosive Atmosphere Flourescent Fixture

    Price: $0.00

    Code: ESW-EXP-380

    SKU:

      

    380 Class Explosive Atmosphere Flourescent Fixture
    PRODUCT OVERVIEW
    The 380 Series is a must for any Explosive Atmosphere Location! (see listings below) This product has five different hub entries at each end enabling the installer to wire the fixture for more desirable angles than a single entry. The center located ballast allows for a more balanced fixture for ease of installation and weight distribution. The 380 Series is available in 2’ & 4’ lengths for 2, 3, & 4 lamp combinations in T5, T5HO, T8, T8HO, T12 & T12HO. Lamps included

    LISTINGS:
    UL 844 listed and labeled - Hazardous Locations: Class I, Division 1, Groups C and D; Class I, Division 2, Groups A, B, C and D
    Class II, Division1 and 2, Groups E, F and G; Class III. UL
    1598A listed and labeled - marine type lighting fixture. Outside Type (salt water)
    UL 1598A testing equivalent to NEMA 4X requirements for hose-down and corrosion resistance.
    UL listed 1598
    UL listed and labeled for use inside paint spray booths and rooms.
    Also meets requirements for National Fire Protection Association Standard 33
    and National Electrical Code Article 516.
    UL C approved and labeled Class I, Division 1, Group C and D
    Class I, Division 2, Groups A, B, C and D
    Class II, Division 1 and 2, Groups E, F and G; Class III.
    NEMA 3, 4X, 7CD, 9EFG.
    Simultaneous presence Class I and Class II
    Suitable for use inside paint spray booths.
    Class I, Zone 1, Group II A
    Class I, Zone 1, Group II B

    HOUSING:
    Factory Sealed, Cast Natural Aluminum (U.S. Foundry) that is lightweight
    Ballast mounted in the center for better balance and low profile.
    (5) 1/2” NPT
    Hubs located at 0°, 45° and 90° angles.

    REFLECTOR:
    One piece painted aluminum reflector with 93% reflective white finish
    LENS: 3/16” Clear tempered glass tubes

    ELECTRICAL:
    120-277 Volt (T5, T5HO & T8 only)
    120 Volts (T8HO, T12, & T12HO)
    220 Volts 50 Hz (T12)
    277 Volts (T8HO, T12, & T12HO)
    347 Volts (T8 & 4 Ft. T12 only)

    APPLICATIONS:
    Hazardous locations, Paint spray booth, Marine/shipboard, Chemical Manufacturers
    Oil Drilling Rigs, Gas Processing Plants, Refineries
    OPTIONS: All Options Ordered Separately - See next page
    Optional Polycarbonate Shield and Stainless Steel Guard.
    EM: Emergency Battery Backup Ballast 120 or 277V MUST SPECIFY
    HB: 93% Reflective specular reflector insert
    PLEASE CALL FOR QUICK QUOTE 888-953-EXIT!